Specifications

MBFPW Series

Model Condenser
coils
Airflow Static
pressure
Cooling
capacity
Heating
capacity
Fan
power
Water
flow
Water
resistance
Noise Weight ^
^
^
^
^
B
A
C
K

T
O

T
O
P
^
^
^
^
^
m3/h Pa kW kW kW m3/h kPa dB (A) kg
MBFPW1.5 4ROWS 1500 135 7.9 14.7 0.375 1.4 1.7 53 90
6ROWS 95 11 17.5 1.9 4.1 100
MBFPW2 4ROWS 2000 120 10.7 19.6 0.375 1.9 3.2 56 95
6ROWS 80 14 25 2.4 7.1 105
MBFPW2.5 4ROWS 2500 180 13.8 24.5 0.45 2.2 5.8 57 115
6ROWS 140 18 32.8 3.1 14.8 135
MBFPW3 4ROWS 3000 190 16.5 29.4 0.55 2.8 8.8 58 120
6ROWS 150 21 38 3.6 19.4 140
MBFPW4 4ROWS 4000 120 22 39 0.375×2 3.78 15.6 61 160
6ROWS 80 28 50 4.8 34.3 180
MBFPW5 4ROWS 5000 175 27.5 45 0.45×2 4.6 25.3 62 185
6ROWS 135 35 54 6 57 210
MBFPW6 4ROWS 6000 230 33 61 0.55×2 5.7 40.1 63 210
6ROWS 190 42 76 7.2 33.6 245
MBFPW7 4ROWS 7000 240 38 70 2.2 13.3 12.9 65 260
6ROWS 200 49 87 8.4 15.1 295
MBFPW8 4ROWS 8000 290 44 80 3 7.6 39.1 65 315
6ROWS 250 56 99 9.6 27.3 360
MBFPW9 4ROWS 9000 300 50 90 2.2 8.5 11.8 66 320
6ROWS 260 63 109 11 14.9 370
MBFPW10 4ROWS 10000 310 55 98 3 9.5 21.4 67 360
6ROWS 260 70 118 12.1 46.5 410
MBFPW12 4ROWS 12000 330 66 122 4 11.4 25 68 410
6ROWS 270 84 192 14.5 53.9 470
MBFPW15 4ROWS 15000 320 85 155 4 14.6 30 70 460
6ROWS 270 112 189 19.2 25.3 520
MBFPW20 4ROWS 20000 350 110 196 2×2.5 18.9 33.5 72 530
6ROWS 300 140 262 24.1 31 610
MBFPW25 4ROWS 25000 400 138 251 7.5 23.8 52.3 74 610
6ROWS 340 175 320 30.1 42.3 690
MBFPW30 4ROWS 30000 450 165 301 2×5.5 28.4 28.7 76 720
6ROWS 390 210 380 36.2 57.8 810
MBFPW35 4ROWS 35000 450 192 361 2×75 33.1 25.5 78 840
6ROWS 390 249 439 42.7 53.8 980

Notes:

  1. Return air conditions:
    a) Cooling: inlet dry bulb temp 27C, wet bulb temp 19.5C; inlet water temp 7C, outlet water temp 12C
    b) Heating: inlet dry bulb temp 15C, inlet water temp 60C, water flow is the same as when cooling
  2. Fresh air condition:
    a) Cooling: inlet dry bulb temp 35C, wet bulb temp 28C; inlet water temp 7C, outlet water temp 12C
    b) Heating: inlet dry bulb temp 7C, inlet water temp 60C, water flow is the same as when cooling
  3. Unit static pressure can be designed according to your requirement
  4. Unit specifications are subject to change without notice. Please refer to unit nameplates for the most accurate specifications


MBFPL Series

Model Condenser
coils
Airflow Static
pressure
Cooling
capacity
Heating
capacity
Fan
power
Water
flow
Water
resistance
Noise Weight ^
^
^
^
^
B
A
C
K

T
O

T
O
P
^
^
^
^
^
m3/h Pa kW kW kW m3/h kPa dB (A) kg
MBFPL2 4ROWS 2000 190 10.7 19.6 0.375 1.9 3.2 56 93
6ROWS 130 14 25 2.4 7.1 100
MBFPL3 4ROWS 3000 240 16.5 29.4 0.55 2.8 8.8 58 150
6ROWS 180 21 38 3.6 19.4 168
MBFPL4 4ROWS 4000 330 22 39 0.375×2 3.78 15.6 61 192
6ROWS 270 28 50 4.8 34.3 200
MBFPL5 4ROWS 5000 340 27.5 45 0.45×2 4.6 25.3 67 224
6ROWS 280 35 54 6 57 240
MBFPL6 4ROWS 6000 280 33 61 0.55×2 5.7 40.1 65 250
6ROWS 220 42 76 7.2 33.6 260
MBFPL8 4ROWS 8000 430 44 80 3 7.6 39.1 67 300
6ROWS 370 56 99 9.6 27.3 338
MBFPL10 4ROWS 10000 490 55 98 3 9.5 21.4 68 419
6ROWS 430 70 118 12.1 46.5 430
MBFPL12 4ROWS 12000 480 66 122 4 11.4 25 70 445
6ROWS 420 84 192 14.5 53.9 460
MBFPL15 4ROWS 15000 520 85 155 4 14.6 30 72 503
6ROWS 460 112 189 19.2 25.3 520
MBFPL20 4ROWS 20000 490 110 196 7.5 18.9 33.5 75 680
6ROWS 430 140 262 24.1 31 700
MBFPL25 4ROWS 25000 690 138 251 11 23.8 52.3 76 860
6ROWS 630 175 320 30.1 42.3 880
MBFPL30 4ROWS 30000 700 165 301 15 28.4 27.4 77 1170
6ROWS 640 210 380 36.2 57.8 1200
MBFPL35 4ROWS 35000 680 193 352 15 33 51 78 1215
6ROWS 620 254 449 42.2 45.5 1250

Notes:

  1. Return air conditions:
    a) Cooling: inlet dry bulb temp 27C, wet bulb temp 19.5C; inlet water temp 7C, outlet water temp 12C
    b) Heating: inlet dry bulb temp 15C, inlet water temp 60C, water flow is the same as when cooling
  2. Fresh air condition:
    a) Cooling: inlet dry bulb temp 35C, wet bulb temp 28C; inlet water temp 7C, outlet water temp 12C
    b) Heating: inlet dry bulb temp 7C, inlet water temp 60C, water flow is the same as when cooling
  3. Unit static pressure can be designed according to your requirement
  4. Unit specifications are subject to change without notice. Please refer to unit nameplates for the most accurate specifications


MBFPD Series

Model Condenser
coils
Airflow Static
pressure
Cooling
capacity
Heating
capacity
Fan
power
Water
flow
Water
resistance
Noise Weight ^
^
^
^
^
B
A
C
K

T
O

T
O
P
^
^
^
^
^
m3/h Pa kW kW kW m3/h kPa dB (A) Kg
MBFPD1.5 4ROWS 1500 100 8.4 15.2 0.32 1.4 9 53 87
6ROWS 60 11.2 18.5 1.9 19.5 96
MBFPD2 4ROWS 2000 120 11.1 19.6 0.375 1.9 11 57 95
6ROWS 80 14.5 24 2.5 22.3 105
MBFPD3 4ROWS 3000 160 16.9 30 0.55 2.9 18 58 120
6ROWS 120 22 37 3.8 28.2 140
MBFPD4 4ROWS 4000 120 22 39.2 0.375×2 3.8 22 59 160
6ROWS 80 28 49 4.8 34.3 180
MBFPD5 4ROWS 5000 180 27.6 50.8 0.45×2 4.7 26 62 185
6ROWS 140 35.1 63.4 6.1 36.5 210
MBFPD6 4ROWS 6000 230 33.1 60.3 0.55×2 5.7 32 63 210
6ROWS 190 42.4 73.2 7.3 37.6 245
MBFPD7 4ROWS 7000 240 38.4 70.1 2.2 6.6 12.9 65 260
6ROWS 200 49.4 87.5 8.5 15.1 295
MBFPD8 4ROWS 8000 280 44 80.5 2.2 7.5 24.9 65 315
6ROWS 240 56.2 100 9.7 52.1 360
MBFPD9 4ROWS 9000 300 51.2 90.8 3 8.8 11.8 66 320
6ROWS 260 63 109 10.8 14.9 370
MBFPD10 4ROWS 10000 300 55 101 3 9.4 25.2 67 360
6ROWS 260 71 118 12.2 50.9 410
MBFPD12 4ROWS 12000 320 66 121 4 11.3 18.8 68 410
6ROWS 270 84 146 14.4 39.9 470
MBFPD15 4ROWS 15000 320 85 155 4 14.6 30 70 460
6ROWS 270 112 189 19.2 25.3 520

Notes:

  1. Return air conditions:
    a) Cooling: inlet dry bulb temp 27C, wet bulb temp 19.5C; inlet water temp 7C, outlet water temp 12C
    b) Heating: inlet dry bulb temp 15C, inlet water temp 60C, water flow is the same as when cooling
  2. Fresh air condition:
    a) Cooling: inlet dry bulb temp 35C, wet bulb temp 28C; inlet water temp 7C, outlet water temp 12C
    b) Heating: inlet dry bulb temp 7C, inlet water temp 60C, water flow is the same as when cooling
  3. Unit static pressure can be designed according to your requirement
  4. Unit specifications are subject to change without notice. Please refer to unit nameplates for the most accurate specifications
We could not find any corresponding parameters, please add them to the properties table

注:1、回风工况:(1)、供冷:进风干球温度27℃,湿球温度19.5℃;进水温度7℃,出水温度12℃;
         (2)、供热:进风干球温度15℃,进水温度60℃,水流量同供冷状态。
  2、新风工况:(1)、供冷:进风干球温度35℃,湿球温度28℃;进水温度7℃,出水温度12℃;
         (2)、供热:进风干球温度7℃,进水温度60℃,水流量同供冷状态。
  3、机组静压可根据您的需要设计选型;
  4、以上参数如因产品改良而更改,恕不另行通知,请以机组铭牌所标参数为准。

Home | E-mail | OA system | Liability | Contact Us | Site Map

 

 © 2020 Copyrights © www.menergy.cn All Rights Reserved. 苏ICP备19056417号-1300.cn